HDER-SSD

Digital Overcurrent Relay

I want to make an inquire
Product details

■  MCU( Microprocessor Control Unit ) Based/2-CT Type 

■  Real Time Processing/Higher Precision
■  Current Setting Range
05Type:0.5~6A/30Type:3~30A/60Type:10~60A
■  Indicating real current on the display
■  Trip cause digital display for easy trouble shooting
■  Reset: Manual(instantaneous)/Electrical(remote)
■  Load selection by DIP switch: Single phase(1P)/Three phase(3P) 
■  Fail-safe(N)/Non-Fail-safe(R) 


Protection:

Protective Item

Trip Time

Description

Over-current

O-TIME

Is

Phase Loss

3 sec


Locked Rotor

0.5sec after elapse of dt

2times OC setting value


Specification:

Current Setting Range

Current

05

0.5 ~ 6A

30

3.0 ~ 30A

60

10 ~ 60A

Starting delay time

D-TIME

OFF

Trip time

O-TIME

0.5, 1~10 sec

Operating t-c characteristic

Over-Current

Definite

Tolerance

Current

±5%

TIME

±5%

Environment

Temperature

Operation

-20 ~60 

Store

-30 ~80 

Humidity

30~85% RH Non-condensing

Control Power

220 : 220VAC±15%, 50/60Hz

110 : 110VAC ±15%, 50/60Hz

Output relay

2-SPST

3A / 250VAC Resistive

Insulation

Between casing and circuit

Over 10MΩ, 500VDC

Dielectric Strength

Between casing and circuit

2000VAC 60Hz, 1min

Between open contacts

1000VAC 60Hz, 1min

between circuit

2000VAC 60Hz, 1min

Reset

Manual/Electrical

Installation

35mm DIN-Rail or Panel Mounting 


Installation dimension drawing:




Circuit diagram:


Contact Us

  • TEL: +86-577-61771181
  • FAX: 86-577-62671829
  • Mobile: +86 13858844068
  • Email: kathy@cnhder.com

Wenzhou Sunao Electric Co., Ltd.

  • Wechat:+86 13858844068

  • Whatsapp:+86 13858844068

  • E-mail:kathy@cnhder.com

  • 技术支持:科讯网络